Power distribution automation enhances power supply reliability and operational efficiency. This article introduces an implementation plan based on Siemens PLCs, focusing on hardware selection, program design, and practical applications.
1. Hardware Configuration
PLC and Expansion Module Selection
The power distribution automation system has high requirements for real-time performance and reliability. It is recommended to use the Siemens S7-1500 series PLC, with the following specific configuration:
-
CPU: 1515-2 PN (with dual Ethernet ports, supports redundant communication)
-
DI Module: SM521 DI32×DC24V (2 units)
-
DO Module: SM522 DO32×DC24V/0.5A (2 units)
-
AI Module: SM531 AI8×13Bit (2 units)
-
AO Module: SM532 AO4×16Bit (1 unit)
I/O Point Allocation Table
| Device Name | Signal Type | PLC Address | Function Description |
|———|———|———|———-|
| Circuit Breaker Status | DI | I0.0-I0.7 | 8-channel circuit breaker open/close status |
| Overcurrent Alarm | DI | I1.0-I1.7 | 8-channel overcurrent protection signal |
| Circuit Breaker Control | DO | Q0.0-Q0.7 | 8-channel open/close control |
| Alarm Indication | DO | Q1.0-Q1.7 | Fault alarm output |
| Current Signal | AI | IW64-IW78 | 8-channel current acquisition |
| Voltage Signal | AI | IW80-IW86 | 3-phase voltage + zero-sequence voltage |
| Remote Control Signal | AO | QW96-QW98 | Output for speed controllers, etc. |
Peripheral Device Selection Criteria
-
Current Transformer: Use high-precision transformers (0.2S grade) to ensure accurate current acquisition
-
Voltage Transmitter: Use isolated transmitters that output 4-20mA standard signals
-
Touch Screen: TP1200 Comfort, 12-inch human-machine interface, supports multi-touch
-
Communication Module: CP1543-1 industrial Ethernet module, supports PROFINET and Modbus TCP
Key Points for System Wiring
-
Separate strong and weak currents, with a distance greater than 30cm
-
Use shielded twisted pairs for analog signals, grounded at one end
-
Use independent relay isolation for digital signals
-
Use UPS for PLC power supply to ensure 30 minutes of operation after power failure
2. Control Program Design
Variable Definition Specifications
// Global Variable DB
DATA_BLOCK "dbGlobal"
STRUCT
// System Status
sysStarted : BOOL; // System startup flag
sysRunning : BOOL; // System running status
sysFault : BOOL; // System fault flag
// Circuit Breaker Status
CB_Status : ARRAY[1..8] OF STRUCT
position : BOOL; // Position status (0-open, 1-closed)
ready : BOOL; // Ready status
fault : BOOL; // Fault status
current : REAL; // Real-time current value
overload : BOOL; // Overload flag
END_STRUCT;
// System Parameters
param : STRUCT
currentLimit : REAL; // Current limit
voltageLimit : REAL; // Voltage limit
delayTime : TIME; // Action delay
END_STRUCT;
END_STRUCT;
Program Architecture Design
The layered structure includes:
-
OB1 Main Loop: Calls various function blocks and manages system status
-
FB1_DataAcq: Data acquisition function block
-
FB2_LogicCtrl: Control logic function block
-
FB3_FaultDetect: Fault detection function block
-
FB4_Protection: Protection function block
-
FB5_Communication: Communication management function block
Function Block Design
FUNCTION_BLOCK "FB2_LogicCtrl"
VAR_INPUT
enable : BOOL; // Enable signal
cbCmd : ARRAY[1..8] OF BOOL; // Circuit breaker control commands
END_VAR
VAR_OUTPUT
cbCtrl : ARRAY[1..8] OF BOOL; // Circuit breaker control outputs
ctrlStatus : WORD; // Control status word
END_VAR
VAR
cmdTimer : TON; // Command timer
prevCmd : ARRAY[1..8] OF BOOL; // Previous command
END_VAR
// Control logic processing
IF enable THEN
FOR i := 1 TO 8 DO
// Detect changes in control commands
IF cbCmd[i] <> prevCmd[i] THEN
// Start timer to avoid misoperation
cmdTimer(IN := TRUE, PT := T#100ms);
IF cmdTimer.Q THEN
// Output control command
cbCtrl[i] := cbCmd[i];
// Record command status
prevCmd[i] := cbCmd[i];
// Reset timer
cmdTimer(IN := FALSE);
END_IF;
END_IF;
END_FOR;
ELSE
// Clear all outputs when the system is disabled
FOR i := 1 TO 8 DO
cbCtrl[i] := FALSE;
END_FOR;
END_IF;
Status Control Design
// System State Machine
CASE systemState OF
0: // Initialization State
IF initComplete THEN
systemState := 1;
END_IF;
1: // Standby State
IF startButton THEN
systemState := 2;
END_IF;
2: // Running State
IF stopButton THEN
systemState := 1;
ELSIF faultDetected THEN
systemState := 3;
END_IF;
3: // Fault State
IF faultReset AND NOT faultDetected THEN
systemState := 1;
END_IF;
END_CASE;
3. Fault Diagnosis and Troubleshooting
Common Fault Analysis
-
Communication Fault
-
Symptoms: HMI cannot display data, communication indicator flashes
-
Causes: Loose network cable, IP address conflict, switch failure
-
Solution: Check network connection, perform ping test, check PLC diagnostic buffer
Circuit Breaker Refusal to Operate
-
Symptoms: No action from circuit breaker after issuing control command
-
Causes: Broken control circuit, coil failure, auxiliary contact issues
-
Solution: Check control circuit voltage, measure coil resistance, check feedback signal
Measurement Data Anomalies
-
Symptoms: Abnormal current/voltage display values
-
Causes: Sensor failure, wiring errors, parameter setting errors
-
Solution: Verify sensors, check wiring, correct range parameters
Using Diagnostic Tools
// Fault Diagnosis Function Block
FUNCTION_BLOCK "FB3_FaultDetect"
VAR_INPUT
cbStatus : ARRAY[1..8] OF BOOL;
cbFeedback : ARRAY[1..8] OF BOOL;
currentValue : ARRAY[1..8] OF REAL;
END_VAR
VAR_OUTPUT
faultCode : ARRAY[1..8] OF WORD;
alarmActive : BOOL;
END_VAR
// Diagnosis Logic
FOR i := 1 TO 8 DO
// Check for inconsistencies between control and feedback
IF cbStatus[i] <> cbFeedback[i] THEN
faultCode[i].%X0 := TRUE; // Position inconsistency fault
END_IF;
// Check for overcurrent
IF currentValue[i] > 1000.0 THEN
faultCode[i].%X1 := TRUE; // Overcurrent fault
END_IF;
// Update overall alarm status
IF faultCode[i] <> 0 THEN
alarmActive := TRUE;
END_IF;
END_FOR;
4. User Interface Design
Interface Layout Description
-
Main Interface: Displays system overview, including single-line diagrams, key parameters, and alarm status
-
Control Interface: Circuit breaker control, parameter settings, manual/automatic switching
-
Trend Interface: Current/voltage curves, historical data queries
-
Alarm Interface: Current alarms, historical alarms, alarm statistics
Parameter Setting Description
The parameter setting interface includes:
- Current limit setting: 0-2000A, step 0.1A
- Voltage limit setting: 0-1000V, step 0.1V
- Action delay setting: 0-10s, step 0.1s
- Communication parameters: IP address, port number, timeout
Operation Monitoring Description
The real-time monitoring system includes:
-
Circuit breaker status indication (open/close, fault)
-
Real-time display of electrical parameters (current, voltage, power)
-
System status indication (running, stopped, fault)
-
Communication status display
Alarm Handling Description
Alarm handling process:
-
After an alarm is triggered, the HMI pops up an alarm window
-
Audible and visual alarm is activated
-
Record alarm information in the historical database
-
The operator confirms the alarm and takes action
-
After troubleshooting, manually reset the alarm
5. System Debugging Methods
Step-by-Step Debugging Method
-
Hardware Testing
-
Check power supply voltage
-
Test I/O channels
-
Verify communication connections
Program Debugging
// Debugging Function Block
FUNCTION_BLOCK "FB_Debug"
VAR_INPUT
debugEnable : BOOL;
testChannel : INT;
END_VAR
VAR_OUTPUT
testResult : BOOL;
END_VAR
IF debugEnable THEN
CASE testChannel OF
1: // Test digital input
testResult := TestDI();
2: // Test digital output
testResult := TestDO();
3: // Test analog input
testResult := TestAI();
END_CASE;
END_IF;
Function Verification
-
Individual device testing
-
Interlocking function testing
-
Protection function testing
Parameter Tuning Steps
-
Set basic parameters (current limit, voltage limit)
-
Calibrate analog inputs (zero point, full scale)
-
Adjust control parameters (PID parameters, delay time)
-
Optimize communication parameters (polling cycle, timeout)
Abnormal Simulation Testing
-
Simulate circuit breaker failure
-
Simulate overcurrent conditions
-
Simulate communication interruption
-
Simulate power supply failure
Performance Verification Key Points
-
Response time testing (<100ms)
-
Communication stability testing (packet loss rate <0.1%)
-
System load testing (CPU usage <60%)
-
Long-term operational stability
This article introduces the key points of designing a power distribution automation system based on Siemens PLCs, covering hardware selection, program design, interface development, and debugging methods. Colleagues are welcome to exchange ideas and discuss to jointly improve the level of power distribution automation.