Mitsubishi FX5U PLC Table Positioning Step Control!

1. Overview

The Mitsubishi FX5U series PLC has a built-in positioning function that supports step control through table positioning commands. This article details the usage of the DRVTBL instruction, as well as the parameter settings and programming implementation for multi-table positioning.

2. Key Instruction Analysis

DRVTBL Instruction

The DRVTBL instruction is used to execute multiple positioning actions based on table data, supporting both step and continuous operation modes.

LD Format

plaintext

DRVTBL S1 S2 S3 S4 D

Parameter Description:

  • S1: Axis Number (K1~K4)
  • S2: Starting Table Row Number
  • S3: Final Table Row Number
  • S4: Operation Mode (K0: Step, K1: Continuous)
  • D: End Flag Soft Element

ST Language Format

plaintext

ENO:=DRVTBL(EN, n1, n2, n3, d1, d2);

Parameter Description:

  • EN: Execution Condition
  • n1: Starting Table Row Number
  • n2: Final Table Row Number
  • n3: Operation Mode (K0: Step, K1: Continuous)
  • d1: Axis Number
  • d2: End Flag

3. Parameter Setting Steps

1. Positioning Parameter Configuration

In the GX Works3 software, navigate to:

<span>Parameters → FX5U CPU Parameters → Module Parameters → High-Speed I/O → Output Function → Positioning → Detailed Settings</span>

Set the pulse output mode to “PULSE/SIGN pulse + Direction” and configure the corresponding output terminals (Y0/Y4, etc.).

2. Positioning Table Settings

In the positioning data settings interface, click on “Axis 1 Positioning Data” to set control methods, positioning addresses, command speeds, and other parameters.

Control methods available:

  • 20: Interpolated Operation (Relative Address Positioning)
  • 22: Interpolated Operation (Absolute Address Positioning)

4. Step Operation Programming Example

1. LD Program

plaintext

DRVTBL K1 K1 K3 K0 M3

  • K1: Axis 1
  • K1: Starting Row 1
  • K3: Ending Row 3
  • K0: Step Mode
  • M3: End Flag

2. Trigger Condition Settings

Trigger the SM5580 special relay through X3 to achieve step transfer:

plaintext

X3 SM5580<span>---| |-------(SET)</span>

3. Program Execution Flow

  1. X4 triggers the DRVTBL instruction to execute the first row of positioning data
  2. After the first row is completed, M3 is set ON
  3. Press X3, SM5580 is set ON, allowing execution of the second row
  4. Repeat until all positioning rows are completed

5. Application Case

Multi-Station Positioning Control

Set 3 positioning points to be executed sequentially in step mode:

Row Number Control Method Positioning Address Command Speed Dwell Time
1 20 1000 5000 100
2 20 2000 3000 200
3 20 1500 4000 150

6. Precautions

  1. Table positioning only supports the CPU body and does not support high-speed input/output pulse modules
  2. When using soft elements, select the power-off retention area
  3. The soft element addresses for each axis must not be duplicated
  4. Step operation must be triggered by an external signal to transfer rows via SM5580

7. References

  1. MELSEC iQ-F FX5 Programming Manual (Instructions, General FUN/FB Section)
  2. Basic Usage of Built-in Positioning Function of FX5U Series PLC
  3. Multi-Table Positioning Step Operation Based on FX5U