Have you ever experienced a situation where your carefully debugged PLC program lost all count values and parameter settings due to an unexpected power failure, requiring the production line to be recalibrated? Or a voltage fluctuation that caused critical data loss, making you work overtime to reset everything? Today, let’s discuss how to protect these valuable data in PLCs.

Why is Power Failure Protection Necessary?

In industrial control, data is wealth. Operating parameters, accumulated count values, recipe data, etc., are the foundation for the normal operation of the system. The factory environment is complex, and power failures and voltage fluctuations occur frequently. Without power failure protection, each power outage may face:

  • Loss of production data, making it impossible to trace
  • Device parameters reset to zero, requiring reconfiguration
  • System status confusion, potentially leading to safety issues

I was once called to handle a fault on a packaging line, which turned out to be caused by a brief power failure that reset the packaging counter to zero, leading the system to mistakenly believe that an entire batch had been produced, directly entering the next process, resulting in significant losses.

Types of Data Storage in PLCs

Understanding the different types of storage in PLCs is the first step in achieving data protection:

  1. Volatile Storage Area: RAM area, data lost after power failure – Such as the M area (intermediate relay area) in Siemens S7-1200 – D registers (data registers) in Mitsubishi PLCs

  2. Non-volatile Storage Area: Battery-backed or EEPROM/Flash storage – Such as the non-volatile M area or DB blocks in Siemens – Non-volatile D registers or file registers in Mitsubishi

Note: Different brands of PLCs have different methods for setting up non-volatile areas, so be sure to consult the relevant manuals before use!

Hardware-Level Power Failure Protection

  1. Battery Backup The most common method of power failure protection is using lithium battery backup. When the external power supply is disconnected, the lithium battery powers the RAM, preventing data loss.
External Power ----> PLC Main Power
|
Lithium Battery ----> RAM Storage Area

Important Reminder: Most PLCs will have an indicator light warning when the battery power is low. Do not ignore this warning! I have seen an engineer lose all parameters of an entire production line because he ignored the battery warning, taking two days to reconfigure everything.

  1. Supercapacitor Backup Some newer PLCs use supercapacitors instead of batteries, providing short-term data retention capabilities, typically lasting from a few hours to a few days.

Software-Level Data Protection

In addition to hardware protection, software-level strategies are more flexible:

  1. Timed Backup to Non-volatile Area
// Triggered once every hour
TON Timer T1(IN := System Running, PT := 1h);

// Trigger backup when timer completes
IF Timer T1.Q THEN
// Copy critical data to non-volatile storage
Non-volatile DB Block.Production Count := Regular DB Block.Production Count;
Timer T1(IN := FALSE);// Reset timer
END_IF;
  1. Immediate Backup on Data Change
// Detect data change
IF Current Production <> Last Backup Production THEN
// Write new data to non-volatile area
Non-volatile DB Block.Production Count := Current Production;
// Update comparison value
Last Backup Production := Current Production;
END_IF;
  1. Using EEPROM/Flash Storage Some PLCs provide special function blocks that can write data to EEPROM or Flash memory:
// Example for Siemens S7-1200/1500
"DataLogWrite"(
REQ := Trigger Condition,
ID := Data Area ID,
DONE => Completion Flag,
ERROR => Error Flag
);

Practical Application Case: Batch Production System

In a pharmaceutical filling system, I used multiple protection strategies:

  1. Store batch number and target quantity in non-volatile DB block
  2. Trigger a data backup every 100 products completed
  3. Automatically perform a complete backup when the system shuts down
  4. Check data consistency at startup, and alarm if anomalies are found

This solution has withstood multiple power failure tests, never losing critical data.

Common Issues and Solutions

  1. Battery Failure Issues – Solution: Set up a maintenance plan for regular battery replacement, typically every 1-2 years

  2. Frequent Writes Leading to Memory Damage – Solution: EEPROM has a write cycle limit, avoid frequent writes to the same area, and consider a strategy of rotating write locations

  3. Incomplete Data Backup – Solution: Use flags to mark backup status, ensuring the backup process is not interrupted

Practical Exercise Suggestions

Prepare a PLC (such as Siemens S7-1200 or Mitsubishi FX3U), write a simple counting program, set up a timed backup function, and then simulate a power failure to test data recovery. Test the power retention capabilities of different storage areas, record results, and analyze.

You can also try to implement a simple “power failure resume” function, backing up the device’s operating status, count values, and other critical parameters, and automatically restoring them to the state before the power failure upon power-up.

Remember: In industrial control, proper data backup is not optional, but a necessity!