WorldFIP Communication in PLC: Industrial Control Network Applications in Power, Transportation, and More

WorldFIP industrial control network communication may be somewhat unfamiliar to those involved in automation. However, this technology is indispensable in large control systems such as power and subway systems. Today, let’s discuss this seemingly complex yet fundamentally simple fieldbus protocol.

Basic Concepts

WorldFIP is a producer-consumer model fieldbus, which can be understood as a large data-sharing platform. For example, it is like a broadcasting system in a factory: data measured by a sensor (producer) is ‘broadcast’ to all devices (consumers) that need this data.

Hardware Connection

WorldFIP adopts a bus topology structure, using twisted pair cables or optical fibers as transmission media. The most common components in the field are:

  • Bus cable: shielded twisted pair
  • Termination resistors: 121Ω (one at each end)
  • Transmission rates: 31.25Kbps/1Mbps/2.5Mbps

PLC Configuration Key Points

  1. Selection of Communication Module

    The commonly used module is the Siemens ET200M series WorldFIP interface module. Configuration steps:

  • Add the WorldFIP module in the hardware configuration
  • Set the station address (ensure it is unique)
  • Configure the variable table (production/consumption variables)
  1. Data Mapping

Copy

//Variable definition example
VAR_GLOBAL
    Speed_Value AT %MW100 : INT;  //Speed value
    Temp_Value  AT %MW102 : REAL; //Temperature value
END_VAR

Practical Application Case

For example, in a thermal power plant:

  1. Boiler area: collection of analog quantities such as temperature and pressure
  2. Turbine area: high-speed data such as speed and vibration
  3. Electrical area: status of digital signals, voltage, and current

Common Issues and Solutions

  1. Communication Interruption
  • Check if the termination resistors are correctly installed
  • Measure the bus voltage (should normally be in the range of 0.75V)
  • Check the module status LED indicators
  1. Data Anomalies
  • Confirm if the variable address mapping is correct
  • Check if the data types match
  • Validate the sampling period settings

Debugging Tools

  • Bus analyzer: can capture communication data packets
  • Oscilloscope: observe the quality of signal waveforms
  • Multimeter: measure termination resistors and supply voltage

Safety Precautions

  1. Do not plug or unplug communication modules while powered
  2. Backup must be done before changing programs
  3. Communication cables must have lightning protection

Optimization Suggestions

  1. Network Planning
  • Reasonably allocate refresh cycles based on control requirements
  • It is recommended to configure redundant channels for critical data
  • Reserve about 20% bandwidth margin
  1. Maintenance Strategy
  • Regularly check communication quality
  • Record fault phenomena and handling methods
  • Establish emergency response plans

Practical exercises:

  1. Configure a simple WorldFIP network, including 1 PLC and 2 remote I/O stations
  2. Implement data exchange of analog and digital signals
  3. Use the analyzer to observe communication data and understand protocol characteristics

Further study can delve into advanced applications such as redundancy configuration and diagnostic functions of WorldFIP. Mastering this technology is very helpful for a deeper understanding of industrial control networks. Feel free to reach out with any questions.