In chemical production, reactor temperature control directly affects product quality and production safety. Today, we will discuss in detail how to build a precise and reliable temperature control system using Siemens PLC.
1. Hardware Configuration
1.1 PLC Selection and Module Configuration
-
Main Unit Selection: S7-1500 CPU 1515-2 PN (with dual Ethernet ports)
-
Analog Input Module: AI 4xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
-
Analog Output Module: AO 4xU/I ST (6ES7532-5HF00-0AB0)
-
Digital Input Module: DI 16x24VDC BA (6ES7521-1BH10-0AA0)
1.2 Key I/O Point Allocation
// Analog Inputs
%IW100: Reactor temperature measurement (PT100, 4-20mA)
%IW102: Jacket inlet temperature (PT100, 4-20mA)
%IW104: Jacket outlet temperature (PT100, 4-20mA)
%IW106: Pressure transmitter (0-10bar, 4-20mA)
// Analog Outputs
%QW100: Heating control valve opening (4-20mA)
%QW102: Cooling control valve opening (4-20mA)
// Digital Inputs
%I0.0: Start button
%I0.1: Stop button
%I0.2: Emergency stop button
%I0.3: Temperature exceeds upper limit
%I0.4: Temperature falls below lower limit
// Digital Outputs
%Q0.0: Running indicator light
%Q0.1: Fault indicator light
%Q0.2: Heating system enable
%Q0.3: Cooling system enable
2. Control Program Design
2.1 Core Temperature Control Function Block
FUNCTION_BLOCK FB_TemperatureControl
VAR_INPUT
Enable : BOOL; // Enable control
SetPoint : REAL; // Temperature setpoint [℃]
ActualValue : REAL; // Actual temperature value [℃]
PID_Manual : BOOL; // Manual/Automatic switch
Manual_Output : REAL; // Manual output value [%]
END_VAR
VAR_OUTPUT
HeatingValve : REAL; // Heating valve opening [%]
CoolingValve : REAL; // Cooling valve opening [%]
ControlMode : INT; // Current control mode
Deviation : REAL; // Temperature deviation [℃]
END_VAR
VAR
PID_Controller : PID_Compact;
OutputValue : REAL;
DeadZone : REAL := 0.5;
END_VAR
// Calculate temperature deviation
Deviation := SetPoint - ActualValue;
// PID controller configuration and execution
PID_Controller(
Setpoint := SetPoint,
Input := ActualValue,
Input_PER := FALSE,
ManualEnable := PID_Manual,
ManualValue := Manual_Output,
Reset := NOT Enable,
Output => OutputValue
);
// Determine heating or cooling mode based on output value
IF OutputValue > DeadZone THEN
HeatingValve := OutputValue;
CoolingValve := 0.0;
ControlMode := 1; // Heating mode
ELSIF OutputValue < -DeadZone THEN
HeatingValve := 0.0;
CoolingValve := ABS(OutputValue);
ControlMode := 2; // Cooling mode
ELSE
HeatingValve := 0.0;
CoolingValve := 0.0;
ControlMode := 0; // Hold mode
END_IF;
2.2 Temperature Segmentation Control Data Block
DATA_BLOCK DB_TempProfile
STRUCT
Segments : ARRAY[1..10] OF STRUCT
Temperature : REAL; // Target temperature [℃]
RampRate : REAL; // Heating rate [℃/min]
HoldTime : TIME; // Hold time
NextStep : INT; // Next segment number
END_STRUCT;
CurrentSegment : INT; // Current segment number
SegmentTimer : TON; // Segment timer
TotalSegments : INT; // Total number of segments
ProfileActive : BOOL; // Process curve active
END_STRUCT;
3. Safety and Redundancy Design
3.1 Temperature Safety Interlock System
FUNCTION_BLOCK FB_TempSafetyInterlock
VAR_INPUT
Temperature : REAL; // Actual temperature
HighLimit : REAL; // High temperature limit
LowLimit : REAL; // Low temperature limit
HighHighLimit : REAL; // Extremely high temperature limit
EmergencyStop : BOOL; // Emergency stop signal
END_VAR
VAR_OUTPUT
SafetyOK : BOOL; // Safety status
AlarmHigh : BOOL; // High temperature alarm
AlarmLow : BOOL; // Low temperature alarm
AlarmHighHigh : BOOL; // Extremely high temperature alarm
ShutdownRequired : BOOL; // Shutdown required
END_VAR
// Temperature range check
AlarmHigh := Temperature > HighLimit;
AlarmLow := Temperature < LowLimit;
AlarmHighHigh := Temperature > HighHighLimit;
// Safety interlock logic
ShutdownRequired := AlarmHighHigh OR EmergencyStop;
SafetyOK := NOT ShutdownRequired AND
NOT (AlarmHigh AND AlarmLow);
// Interlock actions
IF ShutdownRequired THEN
// Execute emergency shutdown procedure
// Close all heating/cooling outputs
// Send alarm notification
END_IF;
3.2 Redundant Temperature Measurement Design
-
Use dual PT100 sensor configuration
-
Sensor signal comparison and fault detection
-
Automatic switch to backup sensor
-
Deviation limit alarm function
4. Human-Machine Interface Design
4.1 Main Operation Screen Layout
-
Process Display Area
-
Real-time temperature trend graph
-
Current temperature/setpoint display
-
Valve opening indicator bar
-
Control mode status
Operation Control Area
-
Temperature setpoint input box
-
Manual/Automatic switch button
-
Start/Stop button
-
Process curve selection
Alarm Information Area
-
Real-time alarm list
-
Historical alarm records
-
Alarm confirmation button
4.2 Parameter Setting Screen
// HMI parameter structure definition
TYPE ST_PIDParameters :
STRUCT
Kp : REAL; // Proportional coefficient
Ti : TIME; // Integral time
Td : TIME; // Derivative time
DeadBand : REAL; // Deadband range
MaxOutput : REAL; // Maximum output
MinOutput : REAL; // Minimum output
END_STRUCT
END_TYPE
5. Fault Diagnosis and Troubleshooting
5.1 Fault Diagnosis Function Block
FUNCTION_BLOCK FB_DiagnosticSystem
VAR_INPUT
SensorStatus : ARRAY[1..4] OF BOOL; // Sensor status
ValveStatus : ARRAY[1..2] OF BOOL; // Valve status
CommStatus : BOOL; // Communication status
END_VAR
VAR_OUTPUT
FaultCode : WORD; // Fault code
FaultDescription : STRING[80]; // Fault description
MaintenanceRequired : BOOL; // Maintenance required
END_VAR
// Fault diagnosis logic
CASE FaultCode OF
16#0001:
FaultDescription := 'Temperature sensor 1 fault';
MaintenanceRequired := TRUE;
16#0002:
FaultDescription := 'Heating valve actuator fault';
MaintenanceRequired := TRUE;
16#0004:
FaultDescription := 'Cooling system circulation pump fault';
MaintenanceRequired := TRUE;
16#0008:
FaultDescription := 'PLC-HMI communication interruption';
MaintenanceRequired := FALSE;
END_CASE;
5.2 Common Fault Quick Handling Table
| Fault Phenomenon | Possible Cause | Handling Method |
|———|———|———|
| Temperature instability | Improper PID parameters | Retune PID parameters |
| Slow heating | Insufficient heating power | Check heater and power supply |
| Valve not actuating | Actuator fault | Check air source and positioner |
| Abnormal readings | Sensor wiring issue | Check wiring and shielding |
6. Debugging Methods and Experience Summary
6.1 Step-by-Step Debugging Process
-
Hardware Check
-
Check the correctness of all wiring
-
Test analog input and output
-
Verify digital signal
Unit Testing
-
Individually test temperature reading
-
Individually test valve control
-
Test alarm system
System Integration Testing
-
Manual mode testing
-
Automatic control testing
-
Abnormal condition simulation
6.2 PID Parameter Tuning Techniques
-
Initial parameter settings: Kp=1.0, Ti=300s, Td=0s
-
Use the critical ratio method for tuning
-
Note the differences in heating and cooling characteristics
-
It is recommended to set a dead zone to prevent frequent switching
Reactor temperature control is a typical process control application. Mastering PLC programming techniques and control strategies can help build a safe and reliable control system. What temperature control challenges have you encountered in your actual projects? Feel free to leave a message for discussion!